Rocklin CA Plumbing, Heating, and Air Conditioning Service

Rocklin Service Area & Reviews

Rocklin Drain Cleaning and Clearing ExpertCrystal Blue Plumbing, Heating & Air provides heater and air conditioning repair, service, installation and services in Rocklin CA and surrounding areas. Check out what some of our customers are saying about Crystal Blue Plumbing, Heating & Air Plumbing, Heating and Air Conditioning services.

We are professionals in…

  • 100% Satisfaction Guarantee
  • Fixed right the first time
  • Non-commissioned technicians
  • Members of the Better Business Bureau
  • We protect your home, we’re licensed & insured

In Rocklin:

Whitney Oaks, Stanford Crossing, Whitney Ranch, Sunset Whitney

 

 

Local Reviews
for Rocklin, CA

Rated 4.9 out of 5 stars based on 47 customer reviews

Map of Rocklin, CA

Amazing Service & Price




The Plumbers did an excellent job fixing the pipes, even under difficult circumstances. We are very happy with Crystal Blue's work.


Map of Rocklin, CA

HVAC




Excellent


Map of Rocklin, CA

Quarterly HVAC maintenance





Map of Rocklin, CA

Great Service, great special!




Tom was awesome! Super nice, quick, cleared clog. A++ Will be contacting for future work.


Map of Rocklin, CA

Great service, Awesome price




Second time I have used Crystal Blue Plumbing and they were great both times. The plumbers were both friendly and explained everything well. This time, Tom let me know what was going on. Fixed the problem as well as was possible (roots in my central line) and gave me an estimate for a long term solution.


Map of Rocklin, CA

Great service




The service person Larry was great and patient at getting out a stone jamming our garbage disposal. He did an awesome job of cleaning up all the pipes underneath the sink and also gave other useful suggestions. I would highly recommend this company!


Map of Rocklin, CA

Great prompt service




Tom arrived earlier then we thought and was very polite. He was. very friendly and explained what he was going to do. He made sure everything was cleaned up before he left. Excellent job!!


Map of Rocklin, CA

Excellent Service




Tom showed up happy and ready to work. We needed the drain in our kitchen cleared and the plumbing underneath the sink was in poor shape and needed to be redone. Tom did such a great job.... never thought I would think the plumbing under the sink looked good, but it looks GREAT!


Map of Rocklin, CA

Quick and Professional Service. A+++++ Rating




When your garbage disposal stops working, you need it fixed quickly. I had the pleasure of working with Tom DeCarli at Crystal Blue Plumbing. The work was done professionally and quickly. I highly recommend Tom and Crystal Blue Plumbing.


Map of Rocklin, CA

Great service




Excellent


Rayne V.

Rayne V.

To install a Navien 240a location in garage will have to also install a vent kit through existing roof jack add a additional drain for condensation to exterior wall add a new expansion tank job includes permit from city also need to confirm the gas supply is sufficient price does not include any gas piping if not correct

Near Lakebreeze Dr, Rocklin, CA 95677
michael E.

michael E.

perform leak search determine where leak is look at options for repair if repairable. If proceeding with the repairs - replace condenser fan capacitor, repair or replace cause of leak, install filter dryer, pressure test, vac system below 500 microns per industry standards, charges system to manufacture specifications Repair prices depending on where leak is can range from $1500-$4200 Nitrogen leak test diagnostic pressured system up to 360 PSI pressure drop to 355 during 2 1/2 hour During that period Sun moved off unit some of refrigerant pressure drop could have been from temperature drop. Could not find leak if there is a leak its very tiny, vibration leak, high pressure leak and fourth option vandalism somebody removing refrigerant one of the first three options most likely the case. Well come back check pressure if pressure has dropped below 350 psi. They leak is present and will need to discuss different methods of trying to discover leak due to it being very ti

Near Sunset Blvd, Rocklin, CA 95765
Jaime C.

Jaime C.

Rocklin CA Run rooter threw clean out in fount yard

Near Midas Ave, Rocklin, CA 95677
michael E.

michael E.

Replace parts per AC maintenance on march/23/2017 installation of new condenser fan motor. due to original motor bearings bad causing motor to overheat and shut down. replaced capacitor do to reading under manufactures tolerance. replaced blower belt do to being overstretched and falling apart. condenser fan motor is OEM from manufacture. capacitor matches OEM capacitor and fan motor. blower belt was set to manufactures spec for new belt adjustment

Near Fairway Dr, Rocklin, CA 95677
Tom D.

Tom D.

Technician will install new ABS pipe to repair existing plumbing fixture inside wall. Technician will reset drywall at completion of job. Price includes one year warranty on parts and labor as well as manufacturers warranty.

Near Aubree Ln, Rocklin, CA 95765
michael E.

michael E.

Capacitor and ECM motor replacement

Near Wild Plains Cir, Rocklin, CA 95765
michael E.

michael E.

Rockland California heating AC service AC diagnostic York split system AC condenser forced air furnace 96% system with ECM motor Diagnostic findings condenser service disconnect unplugged not providing power to unit. homeowner pulled due to unit freezing up. tested electronics in system found bad 70/5 capacitor. tested furnace blower will not come on. Inspection / diagnostic on furnace. tested circuit board operation should turn motor on. tested ECM motor found motor will not turn on. repairs needed capacitor replacement and ECM motor with modular

Near Wild Plains Cir, Rocklin, CA 95765
michael E.

michael E.

Rocklin California heating AC service AC diagnostic Rocklin endurance sports commercial AC diagnostic Diagnostic findings. Visual inspection found condensation water back flowing through drain line. Most likely from other AC units main drain probably plugged this units drain is low point on roof. system inspection unit calling for cooling blower running, compressor outdoor fan not running tested low-voltage circuit found no power coming through safety switches. Turned the power off to test electrical components. found condenser fan capacitor bad. Low refrigerant pressure switch tripped bypass safety switches turned system on. condenser fan motor did not start due to bad capacitor. compressor turned checked refrigerant pressure Found system suction pressure -11 psi. turned system off sitting pressure 10 psi. system extremely low on refrigerant almost empty. Repairs needed for system operation system leak search to determine where leak is. repaire le

Near Sunset Blvd, Rocklin, CA 95765
michael E.

michael E.

Rockland California heating AC service AC diagnostic Goodman split system AC condenser Diagnostic found run capacitor tested good. start capacitor testing bad recommend replacement. wire connections tight no burning or overheating connections. refrigerant pressures good Amp draws compressor 11.6 outdoor fan 1.01 Replaced start capacitor Found no other problems with system at this time

Near Poppy Cir, Rocklin, CA 95765
michael E.

michael E.

Rocklin California heating ac service commercial AC diagnostic carrier package unit Diagnostic found system running compressor, outdoor fan, and blower. found filters plugged. check3rd air temperatures of supply and return 9° difference. check refrigerant pressures R22 system 20 psi low side 112 psi high side right off compressor discharge both Show Low refrigerant charge. found valve stem leaking most likely cause of low refrigerant charge. Recommended repair replace valve stem, charge system to manufacture specifications per charging chart, replace air filters. **Tim waived the $125 diagnostic fee**

Near Sunset Blvd, Rocklin, CA 95765
Sean D.

Sean D.

Found broken waste and overflow concreted into slab not appropriate should be a 12 by 12 opeing to allow any leakage to go below instead of the top

Near Bridal Veil Dr, Rocklin, CA 95677
Tom D.

Tom D.

Technician perform plumbing inspection and found water pressure to be at 120 PSI recommended PSI 60 to 70psi code. This is Extreme and could cause major water damage throughout house recommend prv valve be replace be replaced imediately. Price includes Parts labor and one year warranty leaks labor plus manufacturers

Near Southside Ranch Rd, Rocklin, CA 95677
Tom D.

Tom D.

Technician perform plumbing inspection and found water pressure to be at 120 PSI recommended PSI 60 to 70psi code. This is Extreme and could cause major water damage throughout house recommend prv valve be replace be replaced imediately. Price includes Parts labor and one year warranty leaks labor plus manufacturers

Near Southside Ranch Rd, Rocklin, CA 95677
Tom D.

Tom D.

Estimate to perform complete plumbing inspection and verify KITEC plumbing

Near Southside Ranch Rd, Rocklin, CA 95677
michael E.

michael E.

Rocklin California heating ac service AC maintenance York split system Inspection of drain line sediment buildup in drain line flushed as part of AC maintenance also noticed no elbow on secondary will cause water to blow out past drain pan if water was to backup by not draining out of primary drain line from sediment buildup or by over pressurization from system being zoned. Recommend installing elbow to force water into secondary pan to prevent water damage. Inspection of electrical connections loose in disconnect for incoming power tightened as part of AC maintenance capacitor connection for fan terminal broken (recommend replace terminal for better electrical connection) contacts on contactor pitted and burnt will cause higher amp draws on system and eventual failure to contactor (recommend replacement of contactor) Capacitor 80 / 5 reads 81.2 / 5.2 (good) Amp draw compressor 28.8 actual 16.5 outdoor fan 1.2 actual 1.17 Condenser coil mineral buildup on fins inhibiting heat trans

Near Iroquois Rd, Rocklin, CA 95765
michael E.

michael E.

Rocklin California heating ac service AC maintenance York split system Inspection of drain line sediment buildup in drain line flushed as part of AC maintenance also noticed no elbow on secondary will cause water to blow out past drain pan if water was to backup by not draining out of primary drain line from sediment buildup or by over pressurization from system being zoned. Recommend installing elbow to force water into secondary pan to prevent water damage. Inspection of electrical connections loose in disconnect for incoming power tightened as part of AC maintenance capacitor connection for fan terminal broken (recommend replace terminal for better electrical connection) contacts on contactor pitted and burnt will cause higher amp draws on system and eventual failure to contactor (recommend replacement of contactor) Capacitor 80 / 5 reads 81.2 / 5.2 (good) Amp draw compressor 28.8 actual 16.5 outdoor fan 1.2 actual 1.17 Condenser coil mineral buildup on fins inhibiting heat trans

Near Iroquois Rd, Rocklin, CA 95765
Tom D.

Tom D.

Permit is signed off dropped off at office attached is photos of new vent install at water heater closet old pics of permit card

Near Sunset Blvd, Rocklin, CA 95677
michael E.

michael E.

Rocklin California heating ac service maintenance York gas package unit Capacitor outdoor fan 5 reads 5.1 (good) Amp draw compressor 10.2 reads 6.8 (good) outdoor fan 1.2 reads 1.05 good Electrical wiring found no loose connections all tight Replace air filter checked temp split 20 degrees (good) Found no problems with unit at this time all working

Near Blue Oaks Blvd, Rocklin, CA 95765
michael E.

michael E.

Rocklin California heating ac service maintenance York gas package unit Capacitor outdoor fan 5 reads 5.1 (good) Amp draw compressor 10.2 reads 6.8 (good) outdoor fan 1.2 reads 1.05 good Electrical wiring found no loose connections all tight Replace air filter checked temp split 20 degrees (good) Found no problems with unit at this time all working

Near Blue Oaks Blvd, Rocklin, CA 95765
Sean D.

Sean D.

Found broken waste and overflow concreted into slab not appropriate should be a 12 by 12 opening to allow any leakage to go below instead of the top

Near Bridal Veil Dr, Rocklin, CA 95677
michael E.

michael E.

Unit 1 Filter 16x25x2 (2) belt size a40 found filters plug solid restricting airflow, blower belt extremely loose causing lack of air flow. Both of these issues and age is the cause of a crack in heat exchange chamber - do not recommend use of unit for heating due to this problem. possible leakage of carbon monoxide. replaced air filters as part of this service, recommend replacement of belt due to age and proper tensioning set for belt recommended exchange chamber replacement or replacement of unit Capacitors condenser fan 5 reads 4.7 combustion motor capacitor 4 reads 3.3 both capacitors out of allowable tolerance - recommend replacement of both capacitor Heater relay going out chattering coil going bad - recommend replacement of relay Amp draw combustion motor .46 condenser fan 1.73 compressor 9.24 blower 2.2 Combustion motor and compressor amps good, condenser fan amps High, blower amps lower than what they should be cause loose belt - condenser fan motor most likely will nee

Near Fairway Dr, Rocklin, CA 95677
michael E.

michael E.

Unit 1 Filter 16x25x2 (2) belt size a40 found filters plug solid restricting airflow, blower belt extremely loose causing lack of air flow. Both of these issues and age is the cause of a crack in heat exchange chamber - do not recommend use of unit for heating due to this problem. possible leakage of carbon monoxide. replaced air filters as part of this service, recommend replacement of belt due to age and proper tensioning set for belt recommended exchange chamber replacement or replacement of unit Capacitors condenser fan 5 reads 4.7 combustion motor capacitor 4 reads 3.3 both capacitors out of allowable tolerance - recommend replacement of both capacitor Heater relay going out chattering coil going bad - recommend replacement of relay Amp draw combustion motor .46 condenser fan 1.73 compressor 9.24 blower 2.2 Combustion motor and compressor amps good, condenser fan amps High, blower amps lower than what they should be cause loose belt - condenser fan motor most likely will nee

Near Fairway Dr, Rocklin, CA 95677
michael E.

michael E.

Unit 1 Filter 16x25x2 (2) belt size a40 found filters plug solid restricting airflow, blower belt extremely loose causing lack of air flow. Both of these issues and age is the cause of a crack in heat exchange chamber - do not recommend use of unit for heating due to this problem. possible leakage of carbon monoxide. replaced air filters as part of this service, recommend replacement of belt due to age and proper tensioning set for belt recommended exchange chamber replacement or replacement of unit Capacitors condenser fan 5 reads 4.7 combustion motor capacitor 4 reads 3.3 both capacitors out of allowable tolerance - recommend replacement of both capacitor Heater relay going out chattering coil going bad - recommend replacement of relay Amp draw combustion motor .46 condenser fan 1.73 compressor 9.24 blower 2.2 Combustion motor and compressor amps good, condenser fan amps High, blower amps lower than what they should be cause loose belt - condenser fan motor most likely will nee

Near Fairway Dr, Rocklin, CA 95677
Tom D.

Tom D.

Preform drink clearing through 3 inch two way clean out located front house. Blurred line in approximately 22 to 25 feet heavy root intrusion at that location at this time customer chooses not to run camera and assess she will call and schedule camera or special price. Customer understands line is clear now but there are no warranties on drain clearing. Once the line is cameraed and video we can accurately assess spot repair or full line replacement pricing

Near Midas Ave, Rocklin, CA 95677
Sean D.

Sean D.

Install to customer supplied toilet replace angle stop upstairs bath packing nut was not allowing it to stop leaking

Near Spotted Pony Ln, Rocklin, CA 95765